The Newcastle University research output collection, currently available on ePrints, will shortly be moving to a new open repository platform, Figshare. To prepare for the data migration we have paused adding new content to ePrints, and will resume once the new repository is launched. During this time you will continue to have access to ePrints (but no new content will appear). We will share updates here when available.

Building as a Virtual Power Plant, Magnitude and Persistence of Deferrable Loads and Human Comfort Implications

Lookup NU author(s): Dr Mohammad Royapoor, Dr Mehdi Pazhoohesh, Dr Peter Davison, Professor Haris PatsiosORCiD, Professor Sara Walker

Downloads


Licence

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License (CC BY-NC-ND).


Abstract

This work uses high resolution data from 130 electricity sub-meters to characterise a 12,500m2 commercial building as a virtual power plant (VPP) by assessing magnitude and duration of electrical loads suitable for demand response (DR). In 2018, the building had a peak hourly demand of 48 W/m2 and its electricity consumption (183.2 kWh/m2/yr.) was within low to medium range of air-conditioned UK portfolio. Deferrable loads from heat pumps, air handling units, lifts, lighting, circulating pumps and dry air coolers were used to illustrate building's DR capability over a maximum duration of 4 hours per DR cycle. On average, deferrable loads form 46.4% of total building electricity consumption and across a 4-hour DR cycle can be characterised as having an initial power (and stored energies) of 28kW (401 ± 117kWh); 109kW (571±82 kWh); and finally 138kW (625±18 kWh) for 100%, 41.5% and 24.6% of time respectively. Following a DR event, the HVAC ability to restore original indoor climate was found to be at least twice as fast as climatic drift during the event. A linear regression model was found to be weak in using external temperature to predict the magnitude of aggregated deferrable loads.


Publication metadata

Author(s): Royapoor M, Pazhoohesh M, Davison PJ, Patsios C, Walker S

Publication type: Article

Publication status: Published

Journal: Energy and Buildings

Year: 2020

Volume: 213

Print publication date: 15/04/2020

Online publication date: 30/01/2020

Acceptance date: 16/01/2020

Date deposited: 04/02/2020

ISSN (print): 0378-7788

ISSN (electronic): 1872-6178

Publisher: Elsevier

URL: https://doi.org/10.1016/j.enbuild.2020.109794

DOI: 10.1016/j.enbuild.2020.109794